๐Ÿ How many tons of central air does this house need?

โœ“ Tested & verified Updated: How we calculate this

Central AC tonnage calculator

36,000 BTU/h10.6 kW

The room works out at 36,000 BTU/h โ€” 36,000 is the nearest size actually sold.

Floor area
1,800 sq ft
In tons of refrigeration
3
Working rate
20 BTU/h per sq ft

Use conditioned floor area โ€” heated and cooled space only. An unfinished basement or an unconditioned garage does not belong in this number.

One comfort check a month

Monthly

One thing a month worth measuring, cleaning or switching over before the weather turns โ€” the maintenance side of sizing, in two sentences. No product pitches.

Free, no account. One click unsubscribes and deletes your address.

Try also

How many tons of air conditioning does a house need?

Take the conditioned floor area, multiply by the cooling rate for your climate zone, and divide by 12,000. An 1,800 sq ft house in zone 4 at 20 BTU/h per square foot works out at 36,000 BTU/h โ€” exactly 3 tons, which is why 3 tons is the size half the housing stock has.

Central systems are sold in half-ton steps from 1.5 to 5 tons, so the rounding is coarser than it looks: there is nothing between 3 and 3.5. The cooling rate barely moves across the climate zones โ€” 18 in the far north to 22 on the Gulf โ€” because summer temperature differences are similar almost everywhere. What moves the answer is insulation, glazing and how leaky the house is.

This is a check, not a design. A contractor should run an ACCA Manual J calculation that measures every wall, window, door and duct. If their number differs from this by more than half a ton, that is a conversation worth having: ask which rooms or which windows drove it.

Tonnage is the number on the quote, and it is the one homeowners are least equipped to argue with. This table is the sanity check: conditioned floor area against the size that is normally right for it, before insulation and climate pull it either way.

Conditioned areaZone 2 (Houston)Zone 4 (Baltimore)Zone 6 (Minneapolis)
1,000 sq ft2 tons2 tons1.5 tons
1,400 sq ft2.5 tons2.5 tons2 tons
1,800 sq ft3.5 tons3 tons3 tons
2,200 sq ft4 tons4 tons3.5 tons
2,600 sq ft5 tons4.5 tons4 tons
3,000 sq ft5 tons5 tons4.5 tons

Notice how little the columns differ. Summer is roughly the same problem everywhere; winter is not, which is why the furnace calculator asks the same question and gets an answer that doubles across the table.

Frequently asked questions

How many square feet does a 3 ton AC cover?

Roughly 1,600 to 2,000 sq ft of conditioned space in a typical, reasonably insulated house. The spread is the honest part: the same 3 tons covers 2,000 sq ft in a well-sealed modern build and struggles at 1,600 in a 1960s house with single glazing and no wall insulation. The rate per square foot is a starting point, not a specification.

Is one ton of air conditioning really 12,000 BTU?

Yes, exactly. The unit dates from the ice trade: one ton of refrigeration is the rate of cooling produced by a ton of ice melting over 24 hours, which works out at 12,000 BTU per hour. It has nothing to do with the weight of the equipment, which is a surprisingly common assumption.

What happens if the central unit is oversized?

It short-cycles: the house hits the thermostat setpoint in a few minutes, the compressor stops, and the moisture that a longer run would have condensed out stays in the air. You end up with a cold, damp house, higher bills than a correctly sized system, and compressor wear from repeated starts. Oversizing is the most common fault found in existing installations.

Should I include the basement or the garage?

Include any space with supply and return registers that you actually condition. A finished, ducted basement counts. An unfinished basement with no registers does not, and neither does an attached garage. Counting them adds a half ton to the estimate and pushes you into a unit that will short-cycle for the next fifteen years.

Does a two-storey house change the calculation?

It changes how the system is designed more than how it is sized. Total conditioned area is still the input, but heat rises, so the upper floor peaks later and hotter and the lower floor overshoots. The fix is zoning, damper balancing or a separate system per floor โ€” not more tons.

Why is my contractor's number bigger than this one?

Sometimes for good reasons โ€” Manual J counts west-facing glass, duct losses through an unconditioned attic and infiltration that no rule of thumb can see. Sometimes for a bad one: sizing generously means fewer callbacks in a heatwave and a larger invoice. Asking to see the Manual J output, and which rooms drove it, separates the two quickly.

How we calculate this

Whole-house cooling uses conditioned floor area multiplied by the cooling rate for the IECC climate zone selected โ€” 22 BTU/h per square foot in zone 1 down to 18 in zones 6 and 7 โ€” scaled by ceiling height รท 8 and corrected for insulation (+15% poor, โˆ’10% good). The result is divided by 12,000 BTU/h per ton and rounded up to the half-ton steps central systems are built in, from 1.5 to 5 tons. Sun and occupancy corrections are deliberately not applied at whole-house level: they are room-scale effects that average out across a floor plan, and applying them here would double-count what the climate rate already contains. This is a rule of thumb and does not replace an ACCA Manual J load calculation.

Worked example

With Floor area (sq ft) 1800, Ceiling height (ft) 8, Climate zone Zone 4 โ€” Baltimore, Seattle, Insulation Average โ€” typical home, this page works out 36,000 BTU/h โ‰ˆ 10.6 kW. The room works out at 36,000 BTU/h โ€” 36,000 is the nearest size actually sold.

  • Floor area1,800 sq ft
  • In tons of refrigeration3
  • Working rate20 BTU/h per sq ft

Sources: